Message
System characteristics Cause
Measures
«
AF Cylinder primary pump
■ Circulation pump for
cylinder heating (heat-
ing water side) faulty
■ Circulation volume in
primary store system
too low; cylinder pri-
mary pump (DHW
side) or two-way valve
on primary store sys-
tem faulty.
■ Circulation pump for
cylinder heating:
Test voltage at connec-
tion 2X7.10 and check
pump mechanically;
replace if required.
■ Cylinder primary pump/
two-way valve:
Test voltage at connec-
tion 2X8.12 and check
pump/valve mechani-
cally; replace if
required.
«
B0 Device recognition
Error in recognising
appliance version, incor-
rect coding card or PCBs
faulty.
■ Check sensor input F11
on PCB 3. Do not con-
nect anything to con-
nections 3X1.11 and
3X2.11.
■ Check coding card and
replace if required.
■ Check PCBs and
replace if required.
«
B1 KM BUS EEV
Communication error
with EEV controller
(refrigerant circuit con-
trol)
Check KM BUS connec-
tion. At the connection
between KM BUS and
EEV at terminals 3X5.14
and 3X5.15, a fluctuating
DC voltage between
approx. 20 V and 30 V can
be measured (connec-
tions are parallel to
3X1.25 and 3X2.25).
Check leads/cables;
check power supply to
EEV controller PCB;
replace PCB if required.
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...