123
Function
Explanation
3.
Access rights
Log on as
"Contractor"
by entering code
"5243"
Note
The "Contractor" level remains active either
until key "Standard display"
F
is pressed or if
no input is detected for 30 min.
4.
Programming
System configuration (system scheme and
components)
5.
Sensor temperatures
Checking and matching sensor temperatures
6.
Signal inputs
Checking the signals of connected compo-
nents
7.
Relay (outputs)
Checking the connected functions and external
components with the relay test
Note
Carry out the relay test for every function and
every externally connected component
8.
Mixer
Checking the connected mixers (rotational
direction) or diverter valves
9.
Commissioning
Setting all required parameters, venting the sys-
tem and checking the function of the compo-
nents (see page 126)
10.
The system starts
Note
Messages are displayed by manually controlling
some components during commissioning.
These do not indicate appliance faults.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...