130
Carrying out subscriber check
In conjunction with LON.
Communication with the system devices connected to the fault manager is tested
with a subscriber check.
Preconditions:
■ The heat pump control unit
must be
programmed as the fault manager
(
"Fault manager"
)
■ The LON subscriber number must be
programmed in all control units (see
page 128)
■ The LON subscriber list in the fault
manager must be up to date (see
page 129)
Press the following keys:
1.
To log on as
"Contractor"
, see
2. "Device settings"
.
3. "Contractor level"
.
4. "LON subscriber"
for subscriber
list.
5.
y
/
x
for the required sub-
scriber.
6. "WINK"
Check is enabled.
Displaying:
■
"check"
: Subscriber
check runs;
"LON –
WINK"
flashes for
30 s on the display of
the selected sub-
scriber (if installed).
■
"check OK"
■
"check NOK"
: No
communication
between the two devi-
ces. Check the LON
connection and
codes; restart sub-
scriber check.
7.
Repeat points 5 and 6 to check further
subscribers.
8. "BACK"
to exit the menu.
Instructing the system user
The system installer must hand the operating instructions to the system user and
instruct him/her in the operation of the system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...