129
Updating LON subscriber list
Preconditions:
■ All subscribers must be connected
■ The heat pump control unit
must be
programmed as the fault manager
(
"Fault manager"
)
Press the following keys:
1.
To log on as
"Contractor"
, see
2. "Device settings"
.
3. "Contractor level"
.
4. "LON subscriber"
for subscriber
list.
LON subscriber
1:
BACK
RESET
WINK
2:
3:
OFF
#99
#12
#25
(1.38)
(1.11)
(1.5)
:
:
:
ERROR
OK
A
B
A
LON subscriber number
(page 128)
B
Subnet. node address
(page 160)
Displaying:
■
"OK"
■
"ERROR"
: Subscriber registers a
fault.
■
"OFF"
: No feedback from the sub-
scriber within the timeout period.
5. "RESET"
The subscriber list will be
deleted and recreated
(after approx. 2 min).
6. "BACK"
to exit the menu.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5414 828 GB
Service