167
Temperature sensors type Pt 500
460
20
540
100
Resistance in
Temperature in °C
60
140 180
620
700
780
860
-20
Capturing element "Pt 500"
■ Flow temperature sensor, system
(F13)
■ Buffer temperature sensor (F4)
■ Cylinder temperature sensor top/bot-
tom (F6/F7)
■ Temperature sensor, external heat
source (F20)
■ Flow/return temperature sensor, sec-
ondary circuit (F8/F9)
■ All sensors inside the heat pump
Checking the fuse
Note
Fuse F1 of the heat pump control unit is
located on PCB 1 (cross connect PCB);
see page 76.
Fuse:
■ 6.3 A (slow), 250 V~
■ Max. power loss
≤
2.5 W
Danger
Contact with 'live' components
can lead to severe injury from
electric current.
Before working on the equip-
ment, always ensure that
the
power circuit is also at zero
volt.
Removing the fuse from PCB 1
does
not switch the power cir-
cuit to zero volt
.
Troubleshooting
Repairs
(cont.)
5414 828 GB
Service