163
Display
Explanation
20 nviPM1BlrState
21 nviPM1SupplyT
22 nviPM1BoCState
23 nviPM2BlrState
24 nviPM2SupplyT
25 nviPM2BoCState
26 nviPM3BlrState
27 nviPM3SupplyT
28 nviPM3BoCState
29 nviPM4BlrState
30 nviPM4SupplyT
31 nviPM4BoCState
Rel
Relay status:
Value of network variable
"nvoNodeStatus"
Ó
/
Ò
Precedes sizes displayed:
Ó
Value was received
Ò
Value was sent
Setting via parameters
"Outside temperature"
and
"Time"
AT
Last outside temperature value transferred (if transfer
send/receive is enabled with parameter
"Outside temper-
ature"
)
[ ]
Possible status of outside temperature sensor:
0 OK
6 Not available
Sensor data not evaluated by the software, e.g. if sys-
tem scheme 11 is selected.
8 Fault
Sensor does not show valid values due to short circuit
or lead break
Z
Last transmitted date stamp date/time (if transfer send/
receive is enabled with parameter
"Time"
)
Measures in case the room temperature is constantly too low
1.
Vent the heating circuits.
2.
Check throughput of affected heating
circuits. Recommended temperature
differential between heating flow and
return approx. 8 K.
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...