202
If several subscribers use the current
outside temperature value, this can be
made available centrally by one device
within a system. All other subscribers in
the same system can receive the tem-
perature values.
Note
Only one subscriber within a system may
transmit the outside temperature.
"0"
Device captures the outside tem-
perature via the locally connected
temperature sensor.
"1"
Device captures outside temper-
ature of another LON subscriber
within the same system.
"2"
Device transmits outside temper-
ature. All LON subscribers within
the same system can receive
these values.
Menu
■
"Device settings"
■
"Programming"
■
"Communication"
■
"Outside temperature"
Delivered condition
0
Setting
0 / 1 / 2
Data receive interval
Receive interval for the values and messages transmitted via LON.
If no signal is received for a variable or
message within this cycle time, the heat
pump control unit sets this value or sta-
tus to an internal preset until the corre-
sponding value is received again.
Menu
■
"Device settings"
■
"Programming"
■
"Communication"
■
"Receive Heartbeat"
Delivered condition
20 min
Setting
0 to 60 min
Control settings - communication
Outside temperature via LON
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...