Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Applications
Issue 1.22
5 July 2016
Page 6-29
6 TERMINAL ISOLATED REPEATER (CONTINUED)
Any alarm on the detector circuit (either a short circuit or detector operation) will cause a B1
or a B2 voltage level on the FIP AZC, depending on the battery voltage.
DETECTOR
GAS GROUP 11A OR 11B
GAS GROUP 11C
QTY
CCT LENGTH
QTY
CCT LENGTH
TYPE
PART
BASE
1.0mm²
0.75mm²
1.00mm²
0.75mm²
SMOKE
C29BEx
Z94C
40(M)
3km(R)
2.2km(R)
40(M)
0.9km(C)
0.9km(C)
(100
Ω
)
(100
Ω
)
(90nF)
(90nF)
33
0.97km(C)
0.97km(C)
(97nF)
(97nF)
20
1.1km(C)
1.1km(C)
(110nF)
(110nF)
1
1.3km(C)
1.3km(C)
(130nF)
(130nF)
FLAME
R24BEx
-
7(M)
1.5km(R)
1.1km(R)
2(M)
1.2km(C)
1.1km(R)
(50
Ω
)
(50
Ω
)
(120nF)
(50
Ω
)
HEAT
FW105
-
-
-
-
-
1.3km TOT
1.3km TOT
(100
Ω
TOT)
(100
Ω
TOT)
(130nF)
(130nF)
40(M)
3km(R)
2.2km(R)
40(M)
1.3km(C)
1.3km(C)
HEAT
T54B
-
(100
Ω
)
(100
Ω
)
(130nF)
(130nF)
HEAT
T56B
Z500N
40(M)
3km(R)
2.2km(R)
40(M)
1.13KM(C)
1.3km(C)
(100
Ω
)
(100
Ω
)
(130nF)
(130nF)
FLAME
S231i+
-
11(M)
3KM (R)
2.2KM (R)
11(M)
1.13km(C)
1.13KM(C)
(100
Ω
)
(100
Ω
)
(113nF)
(113nF)
5
1.22km(C)
1.22km(C)
(122nF)
(122nF)
1
1.28km(C)
1.28km(C)
(128nF)
(128nF)
FLAME
S121
-
40(M)
3km(R)
2.2km(R)
32(M)
0.02km(C)
0.02km(C)
(100
Ω
)
(100
Ω
)
(2nF)
(2nF)
20
0.5km(C)
0.5km(C)
(50nF)
(50nF)
10
0.9km(C)
0.9km(C)
(90nF)
(90nF)
1
1.26km(C)
1.26km(C)
(126nF)
(126nF)
FLAME
MS302Ex
M300
40(M)
3km(R)
2.2km(R)
40(M)
0.7km(C)
0.7km(C)
(100
Ω
)
(100
Ω
)
(70nF)
(70nF)
20
1km(C)
1km(C)
(100nF)
(100nF)
1
1.28km(C)
1.28km(C)
(128nF)
(128nF)
ION
MF301Ex
M300
40(M)
(SAME AS MS302Ex)
PHOTO
MR301Ex
M300
40(M)
(SAME AS MS302Ex)
HPO
MR301TEx
M300
40(M)
(SAME AS MS302Ex)
HEAT
MD601Ex
5BEx
40(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
40(M)
1.3KM (C)
1.1KM (R)
HEAT + CO
MDU601Ex
5BEx
40(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
40(M)
1.3KM (C)
1.1KM (R)
ION
MF601Ex
5BEx
40(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
40(M)
1.3KM (C)
1.1KM (R)
PHOTO
MR601TEx
5BEx
36(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
36(M)
1.3KM (C)
1.1KM (R)
CO
MU601Ex
5BEx
40(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
40(M)
1.3KM (C)
1.1KM (R)
FLAME
601FEx
5BEx
6(M)
1.5KM (R)
(50
Ω
)
1.1KM (R)
(50
Ω
)
6(M)
1.3KM (C)
1.1KM (R)
TABLE 6.4.3
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 6-TERMINAL REPEATER
Notes
1.
Circuit lengths quoted are from the isolator to the EOL. An extra 50 Ohms of cable
from the FIP to the isolator is also allowed (1.5km of 1.0mm², 1.1km of 0.75mm²).
The length quoted is the maximum for the corresponding quantity of detectors.
2.
Cable resistance shown is for the circuit, i.e. both cables in the pair. The value of
34
Ω
per km (return) is used for 1 mm².