DETECTORS CERTIFIED WITH F3200 FIP
MAX NO.
TYPE
DESCRIPTION
4mA
SERIES 60
APOLLO HEAT DETECTOR TYPES A, B, C, D
40
SERIES 60
APOLLO PHOTOELECTRIC SMOKE DETECTOR
40
SERIES 60
APOLLO IONISATION SMOKE DETECTOR
40
ALL WITH 45681-200 BASES
MK VIII *
FLAMEGUARD HEAT DETECTOR TYPE A
22
MK VIII *
FLAMEGUARD HEAT DETECTOR TYPE C
11
MK5, MK6 *
INTERTEC HEAT DETECTOR TYPES A, B, C, D
22
(NOTE 9) DETECTOR HAS INTEGRAL LED & TERMINALS
885WP-B ^@
Weatherproof Heat Detector Type B
40
Table IV
OTHER Detectors
SIMPLEX RANGE
MAX NUMBER
TYPE
DESCRIPTION
Iq uA
WITH EOL
4098-9618EA
Type A Heat Detector
100
40*
2
4098-9619EA
Type B Heat Detector
100
40*
2
4098-9621EA
Type D Heat Detector
100
40*
2
4098-9601EA
Photoelectric Smoke Detector
100
40
4098-9603EA
Ionisation Smoke Detector
100
40
4098-9612
Fixed Temperature Heat Detector
100
40
4098-9613
Fixed Tempe Rate of Rise Heat Detector
100
40
4098-9614
Fixed Temperature Heat Detector
100
40
4098-9615
Fixed Tempe Rate of Rise Heat Detector
100
40
*
1
All with Simplex 4098-9788EA base except 4098-9612 to 4098-9615 with 4098-9788 base.
*
2
47E resistor required between AZC+ and deve. See PBG0116.
Table V
SIMPLEX Detectors
REMOTE INDICATORS (LEDS) WITH COMPATIBLE DETECTORS/BASES
REM IND/
BASE
Z51B
Z52B
Z54B
Z54B
MK2
Z55B
Z56
Z500
Z91C
Z94C
MUB
E500
E500 MK2
DET/REM IND
E500
E500 MK2
C23B
R23B
R24B
P76B
Table VI
Tyco Detector/Base & Remote LED Range
The E500 remote indicators are designed to operate across typically 5V.
E500
R = 180
Ω
, V
F
LED = 2.2V typical
E500 Mk2
R = 1.2k
Ω
, V
F
LED = 1.75V typical