F3200/NDU AS4428.1 Installation Manual
Installation & Wiring
Issue 1.22
5 July 2016
Page 5-23
5.6.2
DRIVING MINI-GEN OR ISO 8201 STROBE DRIVER
A relay output of an 8 Relay Module can be used to control and supervision up to 2 Mini-Gen
or ISO 8201 Strobe Driver modules.
One of a number of different wiring methods can be used, depending on the parts available
to adapt the 8 Relay output to provide the required signals and the number of Mini-Gen /
Strobe Driver modules connected.
Figure 5.6.3 shows using one relay output and wiring to the SUP+ pin of the 3 way
Supervised/Unsupervised link pins of the output. This requires soldering or a crimp tool to
crimp the supplied connector onto some 0.1mm
2
-0.35mm
2
wire, to make the connection to
the SUP pin.
Only one Mini-Gen or Strobe Driver module is allowed on this arrangement. However, single
or dual speaker/strobe branch wiring can be supported. The Mini-Gen/Strobe Driver must
be located in the F3200.
It is recommended that 2 x 27k EOL resistors are used. If there is only one branch, fit one
resistor at the end of the wiring, the other at the Mini-Gen/Strobe Driver output terminals - so
that it can be moved to the end of a second branch if it is added later. If there are two
branches, fit a 27k at the end of each branch.
Program the relay output as supervised and select Supervision Enabled during the activated
state.
FIG 5.6.3
USING 1 RELAY OUTPUT WITH 1 MINI-GEN/STROBE DRIVER IN 4-WIRE MODE
+
+
-
-
S
MINI-GEN OR
ISO STROBE DRIVER
2W Link Removed
-
+
EOL
+
-
OR
EOL
+
-
OR
2
nd
Branch
+24V
0V
Panel 24V
Strobe
C NC NO
S
U
Link Not Fitted
Solder or Crimp Pin
8 Relay
Module
Strobe