F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
System Specifications
Page 3-20
5 July 2016
Issue 1.22
3.6
CONTROLS
KEYPAD
Type
:
Polyester Membrane
Keypress
:
Buzzer gives short "beep" for valid keypress
FF Keys
:
EXTERNAL BELL ISOLATE; WARNING SYSTEM ISOLATE; PREV;
NEXT; ACK; RESET; ISOLATE
4x4 Keypad
:
Digits 0-9; Clear/Esc; Enter; 4 x Logic Keys
Zone Functions
-
Alarm, Fault and In-Situ Test; Isolate, Reset, Recall
Ancillary Functions
-
Test, Isolate, Reset, Recall
Relay Functions
-
Test, Isolate, Reset, Recall
System Functions
-
Battery Test, Buzzer Test, Display Test, System Test
-
Bell Test, External Bell Isolate, Warning System Isolate
-
Recall: Alarms, Faults, Isolates, System Faults, History
-
Set time and date
-
Program and view parameters
-
Print and save database
Brigade Functions
-
Acknowledge Alarms
-
View alarms (Next & Prev)
-
Reset acknowledged zone in alarm
-
Isolate acknowledged zone in alarm
-
Brigade Test (via menu)
BUZZER (INTERNAL SOUNDER)
Tone Steady :
Fault, System Fault
Unisolated zone (note 1) or relay supervision fault (note 2)
Sounder re-sounds 8 hours after silence.
Pulsing 2Hz
:
Unisolated zone alarm (note 1)
Slow Pulse
:
Door closed with Database Write Enabled (Lk7) or in Program Mode.
Cadence
:
Zone or In-Situ Test failed (note 3)
Short Pulse
:
Valid keypress
Long Pulse
:
Invalid keypress
Notes:
1)
For zones not mapped to MAF (status only) the buzzer does not turn on (dependent
also on programming of FF).
2)
For relay supervision not mapped to MAF the buzzer does not turn on.
3)
Cadence is repeated fast pulses with a pause.
NDU NZ MODE KEYSWITCHES
Brigade Functions
-
Trial Evacuation, Silence Alarms, Services Restore