F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
System Specifications
Page 3-16
5 July 2016
Issue 1.22
3.5
OUTPUT SPECIFICATIONS
3.5.1
8 ZONE MODULE OUTPUTS
Type
Darlington open collector, switch to 0V
Voltage Rating
28.5V max, "off" state
1.1V max at 100mA “on” state
Current Rating
100mA max per O/P, 0.6A max per module, 1A max per FIP.
Transient Protection
Allows external wiring
Terminations
8 Way demountable screw terminal, 1.5sq mm max. cable
Operation
Programmable
Default
O/C 1 = Zone 1 Alarm
O/C 2 = Zone 2 Alarm, etc.
3.5.2
8 RELAY MODULE OUTPUTS
Form
1 Pole changeover contacts
Voltage-free when unsupervised
Termination
Demountable screw terminals, 1.5sq mm max cable
Rating
30V, 1Adc inductive , 30V, 2Adc resistive
Note The relays are 2 pole, with the second pole terminated on PCB pads.
Operation
Programmable
Supervision
Ref. 3.4.4.
Looping Terminals
2 Sets of 4 joined voltage-free terminals per module
3.5.3
MAF/PSU OUTPUTS
Brigade Relays
Standby
Normally energised, De-energises on battery fail or panel fail
Fault, Isolated, Alarm
Normally de-energised, Energise on active state
Form
1 Pole voltage-free changeover contacts
Termination
Demountable screw terminals
1.5sq mm max cable
Rating
30V, 5A DC resistive; 30V, 3A DC inductive (Rev 1-10)
30V, 2A DC resistive; 30V 1A DC inductive (Rev 11 onwards)
Isolation
1500V rms contact to coil