Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Installation & Wiring
Issue 1.22
5 July 2016
Page 5-39
Outputs ┌────────────┬─┬─┬─┬─┬───────────────┐
│ └─┴─┴─┴─┘ │
spare 1├─┐ 0 Volt ┌─┤
anc defect 2├─┤ ├─┤
anc fire 3├─┤ 26 way FRC ├─┤
fire led 4├─┤ ┌────────────┐ ├─┤
defect led 5├─┤ └───── ─────┘ ├─┤
normal led 6├─┤ ├─┤
Lamp- 7├─┤ ├─┤
Lamp+ 8├─┤ ├─┤
├─┘ +24 Volt └─┤
│ ┌─┬─┬─┬─┐ │
└────────────┴─┴─┴─┴─┴───────────────┘
FIG 5.12.3
TERMINATIONS FROM NZ MODE DISPLAY EXTENDER BOARD ON
UNPROTECTED TERMINATION BOARD (PA0483)
NOTE:
Sprinkler Operated and Trial Evac share the same input and are electrically connected on
the Display Extender Board. On an F4000/MX4428, Input 10 is used as Brigade Test, and
Services Restore (BSR) is not provided.
5.13
NETWORKING
5.13.1
RS485 NETWORKING USING PA0773 RS485 BOARD
A network of up to 32 F3200 panels using dual copper wire pairs can be achieved by fitting
the FP0795 F3200 RS485 Network Kit in each panel. This kit includes an RS485 board
which is mounted on standoffs in the right hand side cabinet wall. It also includes installation
instructions, looms and other hardware.
Where the panels have more than 10 zones or 250 devices/detectors duplicated paths are
required.
5.13.2
I-HUB NETWORKING
The I-HUB is an intelligent network interface board that allows inter-connection of panels in a
ring of copper wire pairs (using RS485 protocol) or fibre-optic cable with OEM fibre-optic
modems.
Up to 64 panels may be connected to the ring.
The I-HUB has a direct TTL connection facility to the F3200 Controller, as well as two RS232
connections. Refer to LT0229 for detail.
The I-HUB is mounted on the standoffs on the inside of the right hand side cabinet wall. The
I-HUB upgrade kit, FP0771, includes the I-HUB board, mounting hardware and inter-
connection looms.
Inputs
16 Sprinkler Operated
15 Trial evac
14 Silence alarms
13 Ext defect
12 Lamp test
11 Brigade Isol/Test
10 BSR
9 Evac Defect