F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Installation & Wiring
Page 5-6
5 July 2016
Issue 1.22
5.1.4
LED DISPLAY INSTALLATION
When LED Displays are required, the 7U inner door (ME0060) or 4U 80 zone door (ME0457)
can be fitted to the standard cabinet directly below the 4U Operator Display with the M6
screws, washers and cage nuts provided. The hinge is on the right hand side. Click the
cage nuts in from the inside. (7U doors cannot be fitted to a small cabinet.)
The flat M6 washers have a sharp edge and a rounded edge. Fit washers to the screws with
the rounded edge facing the metalwork (to avoid damaging the paint.)
The Display Bds mount to the inner door on the standoffs supplied. FZ3031 for LH position,
FP0475 for others, both include the PCB, standoffs, FRC, power leads, diffuser and label
master for ME0060. Use FP1002 when using the ME0457 4U 80 zone display.
Fit the FRCs and Minijump link as shown in Fig 5.1.3.
It is recommended that the LED Display power leads from the MAF/PSU be fitted when more
than 8 Display boards are fitted.
════════════════╗ ╔══════════╗ ╔══════════╗ ╔══════════╗
J13 ║ ║ ║ ║ ║ ║ ║
┌┐ ║ LM0092 ║ ║ ║ ║ ║ ║
CONTROLLER │├──╨────┐ ║ ║ ║ ║ ║ ║
│├──╥──┐ │FRC ║ ║ ║ ║ ║ ║
└┘ ║ │ │ ║ ║ ║ ║ ║ ║
║ │ │ ║ ZONES ║ ─ ─ ─ ║ ZONES ║ ║ ZONES ║
════════════════╝ │ │ ║ 48 TO 64 ║ ║ 17 TO 32 ║ ║ 1 TO 16 ║
│ │ ║ ║ ║ ║ ║ ║
│ │ ║ EXT+ ║ RED ║ EXT+ ║ ║EXT ║
RED┌───┼─┼────╫─o─o──────╫───────╫─o─o──────╫──╫─o LK1 ║
│ ┌─┼─┼────╫─o─o──────╫───────╫─o─o──────╫──╫─o FITTED ║
│ │ │ │ ║ - ║ BLACK ║ - ║ ║ ║
═════════════╗ │ │ │ │ ║ J1 J2 ║ ║ J1 J2 ║ ║ J1 J2 ║
║ │ │ │ │ ╚═╤═╤══╤═╤═╝ ╚═╤═╤══╤═╤═╝ ╚═╤═╤══════╝
J15 ║ │ │ │ └──────┘ │ │ └──── ─ ────┘ │ │ └──────┘ │
LED +o──╫─┘ │ └──────────┘ └────── ─ ──────┘ └──────────┘
DISPLAY -o──╫───┘ DISPLAY FRC
║BLACK
║
║
The order of the Display Boards is as viewed
MAF/PSU ║
from the rear (i.e. inside).
║
║
═════════════╝
FIG 5.1.3
DISPLAY BOARD CONNECTION
Note that a special 26-way FRC loom (LM0092) is required to connect the first Display Board
to the Controller Board. It has one 34 way FRC connector and is included in the F3200 LED
Display Kit (FZ3031). Other options are LM0339 (220mm) and LM0335 (900mm).
For an NDU in New Zealand mode, if a NZ Display Extender board is fitted then it is added
to the end of the display board chain after the last 16 zone display board (if any) and link Lk1
on the last 16 zone display board must be NOT fitted. The NZ Display Extender does not