Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Installation & Wiring
Issue 1.22
5 July 2016
Page 5-25
Figure 5.6.5 shows using two relay outputs to control and supervise 1 or 2 Mini-Gen or
ISO8201 Strobe Driver modules.
2 x 27k EOL resistors are required. If only one Mini-Gen/Strobe Driver is fitted, put one EOL
at the end of the field wiring and the other across the DC IN +ve, -ve terminals. If two
branches or 2 Mini-Gen/Strobe Drivers are used (1 branch each) put the EOL at the end of
each branch.
Program the first relay as supervised and the 2
nd
relay as not, with both relays activated by
the same logic. Also the first relay must be programmed so that supervision is disabled
when the relay is activated.
FIG 5.6.5
USING 2 RELAYS WITH 1/2 MINI-GEN/STROBE DRIVERS
+
+
-
-
S
MINI-GEN OR
ISO STROBE DRIVER
2W Link Fitted
-
+
EOL
+
-
OR
EOL
+
-
OR
2
nd
Branch
+24V
0V
Panel 24V
Strobe
2
nd
Unit
(or spare EOL)
C NC NO
Relay 1
C NC NO
Relay 2
Strobe
S
U
Fit Supervision Link
8 Relay
Module
S
U
Don’t Fit Supervision Link