F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Applications
Page 6-28
5 July 2016
Issue 1.22
OR
FIG 6.4.3.2
F3200 IS CIRCUIT USING 6-TERMINAL REPEATER
Relay or Open Collector
For each AZC there must be either: a corresponding relay (e.g. Module Relay RLn) with
normally closed contacts breaking the supply to the Isolator as shown; or an open collector
output switching the supply 0V to the Isolator as shown. As the open collector is standard
with an 8ZM it is the cheapest alternative.
Programming & Limitations
All detector types require the circuit to be programmed for Mode 1 (Std) with voltage band
B1 programmed as Alarm.
The open collector must be programmed as OCn = ^ZnR, or the Relay must be programmed
as Rn = ZnR (i.e. Zone n not in Reset or Zone n in Reset respectively).
There is no differentiation of voltage bands (B1, B2, B3), i.e., the FIP cannot differentiate
between a short circuit fault, a shorting device such as an MCP, and detector operation on
the same circuit.