F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Applications
Page 6-2
5 July 2016
Issue 1.22
6.1
AS1668 AIR CONDITIONING CONTROL
6.1.1
GENERAL
The following features of F3200 allow it to be easily adapted to make a Fire Fan Control and
Indication Panel (FFCP) (referred to as AS1668 which is the relevant Australian and NZ
Standard):
19" Rack mounting cabinet with standard light grey blank panels available,
including 9½U (plastic), 7U metal (hinged), 4U metal, 3U metal;
Standard module available which includes a PCB module (2 options) with switch
and LEDs, a connector block for field wiring, and labels (see Fig 6.1.1).
Programmable open collector output for driving LEDs (can enter logic equations
for RUN, FAULT, STOPPED);
Programmable relays for fan controls;
Programmable time delays on duct sampling AZCs, with RAD and SAD options;
Programmable AZCs for control inputs with two useable alarm states plus normal
(plus faults) per AZC (i.e. logic equations can differentiate "manual" alarm
(instant) from "detector" alarm (alarm);
Programmable zones, allows non-latching, non-MAF (non-FF), non-
Bells/Ancillaries, status only (i.e. Fan Control Panel output relays can switch
AZCs and the corresponding zones can be programmed as "non-fire" zones with
optional levels of "transparency" within the Fire Alarm System e.g. Faults, Alarms
can be included/not included in the "totals" display and the "recalls").
The standard AS1668 PCB modules are held to the front panel (rear) by a nut on the
threaded shaft of the rotary switch which is attached to the PCB. The LEDs are soldered to
the PCB. The adhesive label is black on clear, and the standard panels are light grey.
The standard colours for RUN, FAULT and STOP (stopped) are red, yellow and green,
respectively.
The KT0113 AS1668 Control Module kit is a convenient way of wiring up some of the circuit
examples described herein. It comes complete with assembly instructions (LT0438) which
include the wiring diagrams 1945-19-3 and 1945-19-4, also included in this section.
The 5 way AS1668 modules (ME0472, KT0478, KT0512) could also be used, but this would
require special wiring of the FRCs to termination boards (PA0483) and then to inputs and
outputs on the F3200
– refer to LT0368.
FIG 6.1.1
STANDARD AS1668 MODULE PANEL LAYOUT