Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Applications
Issue 1.22
5 July 2016
Page 6-21
USING OLD ME0065
– ME0069 GAS CONTROL DOORS (CONTINUED)
7.
Enable supervision on Relay 2 (Evacuate Relay) and use the following logic in the
programming.
Relay 1 (Alert)
:
Supervision enabled, Latching, MAF mapped.
Relay 2 (Evac)
:
Supervision enabled, Latching, MAF mapped.
Relay 1 = Z1A + Z2A + Z3A + Z4A
Relay 2 = Z4A + V1
V1 = Z1A . Z2A . ^Z5A + Z3A
Where:
Z1 = Detection circuit 1
Z2 = Detection circuit 2
Z3 = Gas Start (LGCS)
Z4 = Gas Released (Pressure Switch)
Z5 = Gas Inhibited
Program the panel as otherwise described in Section 6.2.2.
6.2.7
DRAWINGS
The following drawings are included:
1931-47 1 Zone Gas Flood Door (ME0065-69), Circuit Diagram
1937-2 Local Gas Control Station, Circuit Diagram
1931-123 F3200 AS4428 7U 1 Zone Gas Flood Door Loom/Wiring Diagram
1931-124 F3200 AS4428 1U 1 Zone Gas Flood Panel Loom/Wiring Diagram
1931-132 ME0065-69 Gas Door Mods for AVI Mk2 3-Wire Connections