F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Installation & Wiring
Page 5-24
5 July 2016
Issue 1.22
Figure 5.6.4 shows using 2 poles of one relay output to control and supervise 1 or 2 Mini-
Gens or ISO8201 Strobe Driver Modules. The CN0260 and CN0488 connector parts are
required to provide the 2
nd
pole of the relay.
Fit the Supervision link on the 8 relay module.
If using 2 Mini-Gen/Strobe Driver modules they must be co-located.
Use 2 x 27k EOL resistors. If there is one Mini-Gen/Strobe Driver and one branch, fit one
resistor at the end of this branch and the other across the Mini-Gen/Strobe and
–
DC terminals. If there are two branches, or two Mini-Gen/Strobe Drivers (with one branch
each) then fit one 27k resistor at the end of each branch. Program the relay for supervision
enabled and set Supervise in the Activated state to NO!
FIG 5.6.4
USING 2 POLES OF RELAY WITH 1/2 MINI-GEN/STROBE DRIVERS
+
+
-
-