F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Installation & Wiring
Page 5-36
5 July 2016
Issue 1.22
MIMIC DISPLAY (CONTINUED)
These parts are available for constructing displays of this type:
FP0475
FP 16 ZONE LED DISPLAY EXTENDER KIT (C/W LOOM)
FZ3031
16 ZONE LED DISPLAY EXTENDER KIT, RHS POSITION
LM0044
LOOM, DISPLAY EXTENDER FRC 2M 26 WAY
LM0045
LOOM, DISPLAY EXTENDER FRC 5M 26 WAY
(Longer and 3-way looms can be made to special order)
LM0092
LOOM, CONTROLLER TO FIRST DISPLAY 1.2m
PA0483
PCB ASSY, IOR UNPROTECTED TERMINATION BOARD
PA0499
PCB ASSY, NZ DISPLAY EXTENDER BOARD
PA0769
PCB ASSY, 16 O/P MIMIC TERMINATION BOARD, C/W RESISTORS
(As for PA0483 but 3k3 resister per output)
PA0753
PCB ASSY, PICTURE FRAME DISPLAY, 16 LED MIMIC,24V
A suitable cabinet will need to be constructed.
Various FP1600 empty cabinets and the PA0787 FP1600 Mimic Display Board provide an
alternative format.
At the display panel there are two possibilities:
(i)
Geographic Plan Mimic - the FRCs from the NDU are connected to Termination
boards (PA0483). Individual LEDs with series resistors are mounted on the display
panel and wired to these Termination boards. Figure 5.12.1 shows this arrangement.
Alternatively, the PA0769 Termination Board has 3k3 resistors already fitted (gives
7mA LED current which is adequate for interior use).
(ii)
Column Format - where arrangement of zone alarms into columns is acceptable,
LED Mimic Display boards can be used. This simplifies the wiring considerably.
Figure 5.12.2 shows this arrangement.
Note that a special 3-way FRC is required for the Display Extender board, so that the
miscellaneous inputs are accessible in the NDU cabinet. This is not a standard part,
and will need to be made up to suit the application.
5.12.3
PFD MK2 CABINET
The FP0967 PFD Mk2 cabinet can be used to hold 2 x FP1002 16 zone LED Display boards
(32 zones), in either a front or rear service format. The index will need to be marked with the
relevant zone descriptions. Cabling is as described for LED displays in Section 5.1.4.
Note the NDU will need to be mounted adjacent to the PFD cabinet as the FRC cannot be
run externally. If a distance must separate these cabinets, use the PFD Termination board
(PA0772) to provide screw terminals for a 12-way screened cable between the cabinets.
Note also the common Fire, Defect, and Normal LEDs will need to be specially arranged
(either through logic to the zone 1 LEDs or use separate LEDs driven off the NZ Display
Extender).