F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Installation & Wiring
Page 5-16
5 July 2016
Issue 1.22
5.5
WARNING SYSTEM WIRING
The typical configuration allocates the Ancil 3/Bells relay to drive the Warning System, and
has links Lk2-4 fitted so that a switched 24V output is available at the +/- terminals. The
supervision allows for up to 3 branches of wiring, with each requiring its own end of line
resistor (EOLR). The value of the EOLR varies with the number of branches such that the
combined total is always 3K3. The EOLR must be fitted at the end of each branch.
Branches
EOLR
1
3k3
2
6k8
3
10k
The Ancil 3/Bells output can be used to directly control alerting devices such as sounders
(that generate tones to AS2220 or ISO8201), AVIs, strobes etc. If each device does not
have an internal series diode then a series diode must be fitted at each device, as shown in
Fig 5.5.1. The diode must be rated to carry the current of the device.
The AVI Mk2 includes a series diode and multiple units can be connected to a common line,
be supervised, and have the synchronisation wire inter-connected. Note the original AVI
(FP0628) requires an external series diode to be fitted at each device for a supervised
circuit. Multiple original AVIs cannot be synchronised because the sync line carries the
signal and is not supervised.
The Bells +/- output is limited to 2A dc resistive max. (Note that loads such as AVIs, Mini-
Gens are considered resistive, whereas loads such as Solenoids and bells are inductive). A
load of up to 5A dc resistive can be accommodated by use of a Bell Monitor Board and a
separate, 6A dc, inline fuse. See Fig 5.5.5.
A relay on an 8 Relay Module can also be used to control and supervise a circuit of
evacuation devices. This is described in Section 5.6.3.
The Ancil 3/Bells relay can also be used to activate (and supervise) external tone generation
devices such as Mini-Gen, T-GEN 50, Microvac and QE90, and the ISO 8201 Strobe Driver
Module. This is covered in the following sections.
MINI-GEN
The Mini-Gen has an internal diode and can be connected on to the Ancil 3/Bells output with
up to three branches of speakers as per the instructions included with each unit. The 10k
EOLR fitted to each speaker line must be rated at 2W and is supplied with the unit. Refer Fig
5.5.2. If less than 3 branches are required, the 10K 2W is still fitted to the end of each
branch, with the other EOLRs being fitted to the +/- dc input terminals of the furthest Mini-
Gen. Refer to the instructions.
The Mini-Gen can be link selected to produce an Alert tone, an Evac tone, an automatic
change from Alert to Evac after 1 minute, or an automatic change after 3 minutes. If desired,
it can be configured to produce Evac, with a relay switching the tone to Alert. For this, a mini-
jumper is fitted to link V, and the supplied 3 way connector fitted to link A/B with normally
closed relay contacts shorting pin 2 to 3 (position B) to produce Alert. When the contacts
open, the tone will change to Evac. Note that this applies only to Mini-Gen Rev 3 bds with
V2.00 or greater software, and for internal wiring of the relay to the Mini-Gen (i.e. the Mini-
Gen must be mounted within, or adjacent to the FIP.)
A relay output on 8 Relay Module can also be used to drive a Mini-Gen. Refer to Section
5.6.2.