Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
System Specifications
Issue 1.22
5 July 2016
Page 3-7
3.3.5.2
NDU Quiescent and Alarm Currents
Slimline NDU (FP0791/FP0792/FP0793/FP0794)
Operating Voltage
:
24Vdc (18-28V)
Termination
:
For up to 2.5sqmm TPS
Quiescent
Alarm
Current Consumption :
25mA
80mA
Full cabinet NDU (FP0790)
Quiescent
Alarm
Current Consumption (Aust mode)
1
70mA
165mA
Current Consumption (NZ mode)
2
85mA
150mA
1.
Includes controller, MAF/PSU, energised standby relay, PA0773 RS485 Bd, LCD
backlight off in quiescent state.
2.
Includes controller, MAF/PSU, NZ Display Extender, energised standby and alarm
relays, PA0773 RS485 Bd. LCD backlight off in quiescent state.
3.
Refer to Section 3.3.5.1 for additional module currents.
4.
For FP0793 the I-HUB current needs to be added.