F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
System Specifications
Page 3-18
5 July 2016
Issue 1.22
MAF/PSU OUTPUTS (CONTINUED)
+VNBF
1 non-demountable screw terminal, 4sq mm max cable
1 demountable screw terminal, 1.5sq mm max cable
RZDU Comms
Tx, Rx, 0V
3 Wire (+VBF2 available for 4
th
wire)
Transmission Rate
1200 Baud
Protocol
Vigilant F4000
Termination
Demountable screw terminals, 1.5sq mm max cable
3.5.4
CONTROLLER/DISPLAY OUTPUTS
Spare Parallel Outputs
(not fitted)
Number, Rating
6, CMOS 0-5V
Termination
10 Way FRC PCB header, J10
Serial I/O
Printer/Programmer Port
(This is same port as Serial Port 0)
Form
Pseudo RS232, Rx, Tx, 0V signals only
Transient Protection
Allows external wiring
Transmission Rate
9600 Baud
Protocol
ASCII Xon, Xoff
Termination
4 Way .156" male Molex (J1),
9 Way Miniature D available via
LM0041.
Female Pins (socket)
Pin 2 3 5 1 4 6 7 8
Tx Rx 0V
└──┴──┘
└──┘
25 Way Miniature D available via LM0042
Female Pins (socket)
Pin 2 3 7 6 8 20
Rx Tx 0V
└──┴──┘
Also available as 9 way male D connector (J27)
Serial Port 0
10 Way FRC header, J2
UART signals: RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available
Network 1
10 Way FRC header, J7
Network 2
10 Way FRC header, J9
UART signals for Network 1/2
RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available