F3200/NDU AS4428.1 Installation Manual
Document No: LT0255
Appendix A
Page A-6
5 July 2016
Issue 1.22
APPENDIX A2 (CONTINUED)
Remote LEDs
Where remote LEDs are used, mode 2 may have to be selected to give sufficient current for
illumination, depending on the particular LED kit used.
Where mode 2 is selected, some detectors require voltage band B3 to be programmed as
Alarm. See tables I-V.
4.
DELAY TYPE
Delay types 2 and 3 with a delay out of alarm (Delay 2 greater than 0) require a non-latching
detector (e.g. Olsen P76B).
5.
VOLTAGE BANDS
The following tables I-V show the expected alarm voltage band for each type of detector in
Mode 1 (standard) an
d Mode 2 (high current). A “-“ means there is no need to use Mode 2
(and it should not be used).
Where a value other than B2 is shown (e.g. B1 or B3), then that voltage band must be
programmed as Alarm, as well as B2.
Hard Contact Detectors
Hard contact detectors that are not fitted to an electronic base may also be connected
directly across the circuit. Program the detector type as appropriate (e.g. heat, flowswitch)
and voltage band B1 as Alarm (detector operated).
If detectors and MCPs are to be used on the same circuit, with differentiation between them
(e.g. for AVF), then it is necessary to use 15V MCPs and program B3 = Instant Alarm. This
means that 15V MCPs cannot be used on the same circuit as any detector that requires B3
= Alarm.
╔════════════════════════════════════════════════════╤═════════════════╗
║ DETECTORS COMPATIBLE WITH F3200 FIP │ VOLTAGE BANDS ║
║ │ FOR MODES 1 & 2 ║
╟─────────┬──────────────────────────────────────────┼────────┬────────╢
║ TYPE │
DESCRIPTION │ MODE 1 │ MODE 2 ║
╠═════════╪══════════════════════════════════════════╪════════╪════════╣
║ DCD-A │(DCA-B-60R & DCC-A) HEAT DETECTOR TYPE A │ B2 │ B3 ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ DCD-C │(DCA-B-90R & DCC-C) HEAT DETECTOR TYPE C │ B2 │ B3 ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ DFJ-60B │(DFB-60B & DFE-60B) HEAT DETECTOR TYPE B │ B2 │ B3 ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ DFJ-90D │(DFB-90D & DFE-90D) HEAT DETECTOR TYPE D │ B2 │ B3 ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ SIJ-ASN │(SIF-A & SIH-AM) IONISATION SMOKE DETECTOR│ B2 │ B3 ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ SLR-AS │(SLK-A & SLG-AM) PHOTOELECTRIC SMOKE │ B2 │ B3 ║
║ │ DETECTOR │ │ ║
╟─────────┼──────────────────────────────────────────┼────────┼────────╢
║ HF-24A │ULTRAVIOLET FLAME DETECTOR │ B2 │ B3 ║
╚═════════╧══════════════════════════════════════════╧════════╧════════╝
Table I
HOCHIKI Detector Range