82
H9 ASD Installation and Operation Manual
Manual Torque Boost 1
Program
Fundamental
Motor Set 1
The
Manual Torque Boost 1
function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 1
(
F014
) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive
Torque Boost
level may cause nuisance
tripping and mechanical stress to loads.
Direct Access Number — F016
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Overload Protection Configuration
Program
Protection
Overload
This parameter is used to protect the motor from an over-current condition. The
type of motor being used and the
Overload Stall
setting is selected here to
better match the application.
This parameter setting may extend the
Over-Voltage
Stall
time settings.
This parameter may be affected by the setting of the
Power Running Stall
Continuous Trip Detection Time
(
F452
).
Settings:
0 — Overload Trip without Stall
1 — Overload Trip with Stall
2 — No Overload without Stall
3 — Stall Only
4 — V/f Motor-Overload without Stall
5 — V/f Motor-Overload with Stall
6 — V/f Motor-No Overload without Stall
7 — V/f Motor-Stall Only
Direct Access Number — F017
Parameter Type —
Selection List
Factory Default —
O/L Trip No Stall
Changeable During Run —
Yes
F016
F017