196
H9 ASD Installation and Operation Manual
MON 2 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON2
output terminal.
The
MON2
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F692
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
MON 2 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON2
terminal.
Set the assigned function of parameter
F674
to zero and then set this parameter
to a zero output.
See parameter
F674
for more information on this setting.
Direct Access Number — F693
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Parameter Write Lock Out
Program
Utilities
Prohibition
This parameter
Enables/Disables
the
Run
and
Stop
keys.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F700
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Display Units for Voltage and Current
Program
Utilities
Display Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Direct Access Number — F701
Parameter Type —
Selection List
Factory Default — %
Changeable During Run —
Yes
Display Unit Multiplication Factor
Program
Utilities
Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example:
An output frequency of 100 Hz would be displayed as 50 Hz if
using a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters are not affected by this
setting (i.e.,
F364
,
F365
,
F367
, and
F368
).
Direct Access Number — F702
Parameter Type —
Numerical
Factory Default —
0.00 (OFF)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
F692
F702