170
H9 ASD Installation and Operation Manual
Deceleration Time 4
Program
Special
Accel/Decel 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the
Maximum Frequency
to 0.0 Hz for the
4 Deceleration
profile. The
Accel/Decel pattern may be set using
F502
. The minimum Accel/Decel time
may be set using
F508
.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
deceleration times.
Direct Access Number — F515
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Acceleration/Deceleration Pattern 4
Program
Special
Accel/Decel 1 – 4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
4 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F516
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Acceleration/Deceleration Switching Frequency 3
Program
Special
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel 3
profile to the
Accel 4
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F517
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Pattern Operation Selection
Program
Pattern Run
Pattern Run
Pattern Run
operation is enabled by selecting
Seconds
or
Minutes
as a unit of
measure for the
Operation Time
setting for the selected
Preset Speeds
.
See Parameter
F523
for more information on
Selections
and
Group Speeds
setup.
Settings:
0 — Disabled
1 — Enabled (Units in Seconds)
2 — Enabled (Units in Minutes)
Direct Access Number — F520
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Pattern Operation Mode
Program
Pattern Run
Pattern Run
This parameter sets the start condition of subsequent
Pattern Runs
after the
initial
Pattern Run
has been terminated or has completed its programming.
Settings:
0 — Reset After Stop
1 — Continue After Stop
Direct Access Number — F521
Parameter Type —
Selection List
Factory Default —
Reset After Stop
Changeable During Run —
No
F515
F521