86
H9 ASD Installation and Operation Manual
Low-Speed Signal Output Frequency
Program
Terminal
Reach Settings
The
Low-Speed Signal Output Frequency
parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is equal to or above this setting (see
Table 8 on pg. 239
for the
available output assignments).
Direct Access Number — F100
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Speed Reach Frequency
Program
Terminal
Reach Settings
The
Speed Reach Frequency
sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter
F102
, activates the assigned
output terminal for the duration that the ASD output is within the bandwidth
specified (see
Table 8 on pg. 239
for the available output assignments).
Direct Access Number — F101
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Speed Reach Detection Band
Program
Terminal
Reach Settings
This parameter sets the bandwidth of the
Speed Reach Frequency
(
F101
)
setting.
Direct Access Number — F102
Parameter Type —
Numerical
Factory Default —
2.50
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Forward/Reverse Run Priority Selection
Program
Terminal
Input Special Functions
The
Forward/Reverse Priority Selection
determines the operation of the ASD
if the
F
and
R
control terminals are activated simultaneously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combinations of the
F
and
R
terminal settings if the
Reverse
option is chosen.
The
Suspend
setting will decelerate the motor to a stop regardless of the
rotation direction when both the
F
and
R
control terminals are activated.
Direct Access Number — F105
Parameter Type —
Selection List
Factory Default —
Suspend
Changeable During Run —
No
Simultaneous F and R activation.
ow Speed
each
requency
F100
F105
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]