H9 ASD Installation and Operation Manual
195
AM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
AM
terminal.
Set the function set at
F670
to zero and then set this parameter to zero for
proper operation.
See
F670
for more information on this setting.
Direct Access Number — F686
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
MON 1 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON1
output
terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F688
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
Yes
MON 1 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON1
output terminal.
The
MON1
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F689
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
MON 1 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON1
terminal.
Set the assigned function of parameter
F672
to zero and then set this parameter
to a zero output.
See parameter
F672
for more information on this setting.
Direct Access Number — F690
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %
MON 2 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON2
output
terminal.
See parameter
F674
for more information on this setting.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F691
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
Yes
F686
F691