H9 ASD Installation and Operation Manual
83
Preset Speed 1
Program
Frequency
Preset Speeds
Up to fifteen (15) output frequency values that fall within the
Lower-Limit
and
the
Upper-Limit
range may be programmed into the drive and output as a
Preset Speed
. This parameter assigns an output frequency to binary number
0001 and is identified as
Preset Speed 1
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
.
Perform the following setup to allow the system to receive
Preset Speed
control input at the
S1 – S4
terminals:
1.
Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Block
.
2.
Program
Terminal
Input Terminals
S1
(set to
Preset Speed 1
;
LSB of 4-bit count). Repeat for
S2
–
S4
(MSB of 4-bit count) as
Preset
Speed 2
–
4
, respectively (all
Normally Open
).
3.
Program
Frequency
Preset Speeds
Preset Speed
1
(set an output
frequency as
Preset Speed 1
; repeat for
Preset Speeds 2
–
15
as required).
4.
Program
Pattern Run
Operation Mode
Preset Speed Operation
Mode
Enabled/Disabled
.
Select
Enabled
to use the direction, accel/decel, and torque settings of the
Preset Speed
being run. The torque settings used will be as defined in
F170
–
F181
and as selected via the associated discrete input terminals
V/f
Switching 1
and
2
in
Table 5 on pg. 234
.
Select
Disabled
to use the speed setting only of the
Preset Speed
being run.
5.
Place the system in the
Remote
mode (Local/Remote LED Off).
6.
Provide a
Run
command (connect F and/or R to CC).
Connect
S1
to
CC
to run
Preset Speed 1
(
S1
to
CC
= 0001 binary).
With
S1
–
S4
configured to output
Preset Speeds
(
F115
–
F118
), 0001 – 1111
may be applied to
S1 – S4
of the
Terminal Board
to run the associated
Preset
Speed
. If bidirectional operation is required,
F
and
R
must be connected to
CC
,
and
Preset Speed Operation Mode
must be set to
Enabled
at
F560
.
With
S1
being the least significant bit of a binary count, the
S1 – S4
settings
will produce the programmed speed settings as indicated in the
Preset Speed
Truth Table
to the right.
Preset Speeds
are also used in the
Pattern Run
mode.
Direct Access Number — F018
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed Truth Table
Preset Speed 2
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as
Preset Speed 2
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F019
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
eset Speed 1
Preset
S4
MSB
S3
S2
S1
LSB
Output
1
0
0
0
1
F018
2
0
0
1
0
F019
3
0
0
1
1
F020
4
0
1
0
0
F021
5
0
1
0
1
F022
6
0
1
1
0
F023
7
0
1
1
1
F024
8
1
0
0
0
F287
9
1
0
0
1
F288
10
1
0
1
0
F289
11
1
0
1
1
F290
12
1
1
0
0
F291
13
1
1
0
1
F292
14
1
1
1
0
F293
15
1
1
1
1
F294
Note:
1 = Terminal connected to
CC
.
eset Speed 2
F018