264
H9 ASD Installation and Operation Manual
Cable/Terminal/Torque Specifications
Installation should conform to the
NEC
Article 110
(Requirements for Electrical Installations), all regulations
of the Occupational Safety and Health Administration, and any other applicable national, regional, or
industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the H9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the H9 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the H9 ASD and
Do
Not
include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
For further installation information see the section titled
Installation and Connections on pg. 14
.
Note:
(*) Indicates that the item is one of a set of two parallel cables.
Table 20. 230-Volt H9 ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130H9U
MCP Rating
(Amps)
Wire/Cable Size
Lug Size Range
Terminal
Board
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
Recommended Maximum
3Ø-Input
3Ø-Output
In-Lbs./Nm
2010
15
14
10
14 to 8
20
(3-core shield)
Torque to 5.3/0.6
11.5/1.3
2015
2025
2035
30
2055
10
2080
50
8
8
12 to 8
17.7/2.0
2110
2160
75
6
3
8 to 3
21/2.4
2220
100
4
2270
125
3
2330
150
2
2
12 to 1/0
4 to 1/0
50/5.7
53/6
2400
175
1/0
4/0
6 to 250
2 to 300
275/31
168/19
2500
200
2/0
2600
250
3/0
2750
300
4/0
210K
400
*3/0
*1/0
6 to 250
275/31
212K
500
*250
*250