H9 ASD Installation and Operation Manual
Stall Prevention Factor 1
Program
Protection
Stall
This parameter is to be adjusted in the event that the motor stalls when operated
above the base frequency.
If a momentary heavy load occurs the motor may stall before the load current
reaches the stall prevention level setting of
F601
.
A drop in the supply voltage may cause fluctuations of the load current or may
cause motor vibration. A gradual adjustment of this parameter may alleviate
this condition.
Start with a setting of 85 at these parameters and gradually adjust them from
there one at a time until the desired results are produced.
Adjustments to this parameter may increase the load current of the motor and
subsequently warrant an adjustment at the
Motor Overload Protection Level
setting.
Direct Access Number — F416
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 10
Maximum — 250
Torque Command Selection
Program
Torque
Torque Control
When operating in the
Torque Control
mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad) (
F725
Setting)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Direct Access Number — F420
Parameter Type —
Selection List
Factory Default —
RX
Changeable During Run —
Yes
Tension Torque Bias Input
Program
Torque
Torque Control
This parameter
Enables/Disables
the
Tension Torque Bias
input function.
This feature is enabled by selecting a
Tension Torque Bias
input signal source.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Direct Access Number — F423
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
F416
F423