H9 ASD Installation and Operation Manual
My Function Time Data 4
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 4
terminal.
The applied discrete input signal must be present at the input terminal of the H9
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F931
Parameter Type —
Numerical
Factory Default — 0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 5
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 5
terminal.
The applied discrete input signal must be present at the input terminal of the H9
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F932
Parameter Type —
Numerical
Factory Default — 0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Count Data 1
Program
My Function
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output
COUNT1 (ON Timer)
.
COUNT1 (ON Timer)
outputs a 1 upon reaching the threshold setting of this
parameter.
Direct Access Number — F933
Parameter Type —
Numerical
Factory Default — 0
Changeable During Run —
Yes
Minimum — 0
Maximum — 9999
Units — Pulses
My Function Count Data 2
Program
My Function
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output
COUNT2 (ON Timer)
.
COUNT2 (ON Timer)
outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number — F934
Parameter Type —
Numerical
Factory Default — 0
Changeable During Run —
Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Input Function Target 1
Program
My Function
My Function Unit 4
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the programmable
Input Function Target 1
terminal.
This setting assigns the function of the programmable
Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 7 on pg. 238
,
Table 8 on pg. 239
, or
Table 10 on pg. 241
.
See
F977
for more information on this parameter.
Direct Access Number — F935
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
F931
F935