268
H9 ASD Installation and Operation Manual
Short Circuit Protection Recommendations
Table 22. 230/240 and 400/480-Volt ASD Recommended Circuit Breaker Selection.
Model Number
VT130H9U
HP
Continuous Output Current
(Amps)
Circuit Breaker Part Number
2010
0.75
3.2
HLL36015
2015
1.0
4.2
2025
2.0
6.8
2035
3.0
9.6
HLL36025
2055
5.0
15.2
2080
7.5
22.0
HLL36040
2110
10
28.0
HLL36050
2160
15
42.0
HLL36070
2220
20
54.0
HLL36090
2270
25
68.0
HLL36100
2330
30
80.0
2400
40
104
HLL36125
2500
50
130
HLL36150
2600
60
154
JLL36200
2750
75
192
210K
100
248
JLL36250
212K
125
312
LIL36300
4015
1.0
2.1
HLL36015
4025
2.0
3.4
4035
3.0
4.8
4055
5
7.6
HLL36025
4080
7.5
11.0
4110
10
14.0
HLL36040
4160
15
21.0
HLL36070
4220
20
27.0
4270
25
34.0
HLL36090
4330
30
40.0
HLL36100
4400
40
52.0
HLL36125
4500
50
65.0
HLL36150
4600
60
77.0
JLL36200
4750
75
96.0
JLL36225
410K
100
124
JLL36250
412K
125
156
LIL36300
415K
150
180
420K
200
240
LIL36400
425K
250
302
430K
300
361
LIL36450
435K
350
414
LIL36500
440K
400
477
Consult NEC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]