H9 ASD Installation and Operation Manual
Pattern Group 1 Selection 1
Program
Pattern Run
Speeds
Groups of configured
Preset Speeds
may be selected and run from this screen.
The execution of grouped
Preset Speeds
in this manner is called a
Pattern
Run
.
One to eight user-selected
Preset Speeds
may be run sequentially for a user-set
number of repetitions. The group of user-selected
Preset Speeds
is called a
Pattern Group
. The
Pattern Run
function executes the user-set
Pattern
Group
.
Pattern Group
1
is comprised of up to 8
Selections
with each
Selection
being
1 of 15 possible
Preset Speed
settings.
Skip
may be selected to ignore a
Selection
.
This parameter allows the user to choose one configured
Preset Speed
that is to
be used as
Selection 1
(of 8) for
Pattern Group 1
. See
F018
for information on
configuring the individual
Preset Speeds
. Parameters
F524
–
F530
may be
setup for subsequent
Selections
2
–
8
.
One
Preset Speed
number (1 – 15) or
Skip
is selected for
Selection 1
(
F523
).
The number of times to repeat
Pattern Group 1
is selected at
F522
. Set this
value to
255
to run forever.
Setup
Pattern Group 2
at
F531
–
F539
if more
Preset Speed
entries are
required.
Pattern Run Setup
(for Pattern Group 1)
1.
From Program
Pattern Run
Speeds
, select the
Preset Speeds
that are
to be used as the
Pattern Group 1
set of
Selections
. Select a speed from
the 1 – 15 configured presets; 1 speed number per
Selection
. Set any
unused
Selections
to
Skip
.
2.
From Program
Pattern Run
Pattern Run
Pattern Operation
Selection
, enable the
Pattern Run
mode of operation by selecting
Seconds
or
Minutes
as the unit of measure for the
Operation Time
setting.
3.
From Program
Pattern Run
Operation Time
, set the run-time for
each
Preset Speed
selected in step
1
.
4.
Configure two unused discrete input terminals for
Pattern Operation
Group 1
and
Pattern Operation Trigger Signal
.
Note:
Activation of the
Pattern Operation Group 1
discrete input
terminal is required to enable
Pattern Group 1
for use.
Activation of the
Pattern Operation Trigger Signal
discrete
input terminal starts the
Pattern Group 1
pattern run.
5.
From Program
Pattern Run
Pattern Run
Pattern 1 Repeat
, set to
the number of times that
Pattern Group 1
is to be run. Set to
255
to run
forever.
6.
From Program
Pattern Run
Pattern Run
Pattern Operation
Mode
, set the end-of-pattern command to
Reset
or
Continue
.
7.
From the
Remote
mode (
Local/Remote
light is off), initiate a
Run
command (i.e.,
F
and/or
R
terminal
On
).
8.
Connect the
Pattern Operation Group 1
input terminal to
CC
.
9.
Connect the
Pattern Operation Trigger Signal
input terminal to
CC
and
the
Pattern Run
will start and continue as programmed.
10. Open the
Pattern Operation Trigger Signal
connection to
CC
to stop the
Pattern Run
before its conclusion if required.
Direct Access Number — F523
Parameter Type —
Selection List
Factory Default —
Skip
Changeable During Run —
No
Minimum — Skip
Maximum — 15
Units — Preset Speed Number
Pattern Group 1
Selection
F523 F524 F525 F526 F527 F528 F529 F530
1
2
3
4
5
6
7
8
P
res
et
S
p
ee
d
Nu
m
b
er
Skip Skip Skip Skip Skip Skip Skip Skip
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
F523
F523
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]