200
H9 ASD Installation and Operation Manual
Panel Reset Lock Out
Program
Special
Operation Panel Parameters
This parameter is model-specific and has no function on the H9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F735
Parameter Type —
Selection List
Factory Default —
Unlocked
Changeable During Run —
Yes
Command Mode/Frequency Mode Change Lock Out
Program
Utilities
Prohibition
This parameter is model-specific and has no function on the H9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F736
Parameter Type —
Selection List
Factory Default —
Locked
Changeable During Run —
Yes
Lock Out All Keys
Program
Utilities
Prohibition
This parameter is model-specific and has no function on the H9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F737
Parameter Type —
Selection List
Factory Default —
Unlocked
Changeable During Run —
Yes
Trace Selection
Program
Utilities
Trace
In conjunction with parameter
F741
–
F745
, this parameter is used to monitor
and store 4 ASD output waveform data points. The data may be read and stored
as a function of a trip (At Trip) or it may be initiated by the activation of a
discrete terminal activation (At Trigger).
Set a discrete input terminal to
Trace Back Trigger Signal
and activate the
terminal to initiate the
At Trigger
read/store function.
Table 9 on pg. 240
lists the items that may be selected for the data read/store
function along with the associated communication number for each selection.
The duration of the read/store cycle for the selected items is set at parameter
F741
.
To acquire and store the data a communications device and a PC are required.
The H9 ASD supports the following communications protocols: RS485
(MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol, CC-Link, ProfiBus,
and DeviceNet (Refer to the manual of each protocol type for more
information).
Trace data may be viewed graphically via Program
Utilities
View Trace
Data
.
Settings:
0 — None (Disabled)
1 — At Trip
2 — At Trigger
Direct Access Number — F740
Parameter Type —
Selection List
Factory Default —
At Trip
Changeable During Run —
Yes
F735
F740