H9 ASD Installation and Operation Manual
239
Table 8. Output Terminal Assignments,
My Function Input Setting
Assignments, and Parameter/Input
Setting Numbers for the
FLA
/
B
/
C
,
O1A
/
O1B
(OUT1),
O2A
/
O2B
(OUT2),
OUT3
–
OUT6
, and
R1
–
R4
.
Discrete Output Terminal Assignment Selections
Input
Setting
Param.
Setting
Function
Input
Setting
Param.
Setting
Function
1000
0
Lower-Limit Frequency
1086
86
Error Code Output 4
1002
2
Upper-Limit Frequency
1088
88
Error Code Output 5
1004
4
Low-Speed Signal
1090
90
Error Code Output 6
1006
6
Acceleration/Deceleration Completion
1092
92
Specified Data Output 1
1008
8
Speed Reach Signal
1094
94
Specified Data Output 2
1010
10
Failure FL (All Trips)
1096
96
Specified Data Output 3
1012
12
Failure FL (Except EF, OCL, EPHO, OL2)
1098
98
Specified Data Output 4
1014
14
Over-Current (OC) Alarm
1100
100
Specified Data Output 5
1016
16
ASD Overload (OL1) Alarm
1102
102
Specified Data Output 6
1018
18
Motor Overload (OL2) Alarm
1104
104
Specified Data Output 7
1020
20
Over-Heat Alarm
1106
106
Light Load
1022
22
Over-Voltage Alarm
1108
108
Heavy Load
1024
24
Main Circuit (MOFF) Under-Voltage Alarm
1110
110
Positive Torque Limit
1026
26
Low-Current Alarm
1112
112
Negative Torque Limit
1028
28
Over-Torque Alarm
1114
114
External Rush Suppression Relay Activated
1030
30
DBR Overload Alarm
1118
118
Completion of Stop Positioning
1032
32
Emergency Off Active
1120
120
L-STOP
1034
34
Retry Active
1122
122
Power Failure Synchronized Operation
1036
36
Pattern Operation Switching Output
1124
124
Traverse in Progress
1038
38
PID Deviation Limit
1126
126
Traverse Deceleration Active
1040
40
Run/Stop
1128
128
Part Replacement Alarm
1042
42
Serious Failure (OCA, OCL, EF, Phase Failure, etc.) 1130
130
Over-Torque Alarm
1044
44
Light failure (OL, OC1, 2, 3, OP)
1132
132
Frequency Command ½ Selection
1046
46
Commercial Power/ASD Switching Output 1
1134
134
Failure FL (Except Emergency Off)
1048
48
Commercial power/ASD switching Output 2
1222
222
My Function Output 1
1050
50
Cooling Fan On/Off
1224
224
My Function Output 2
1052
52
Jogging Operation Active (Jog Run Active)
1226
226
My Function Output 3
1054
54
Panel/Terminal Board Operation Switching
1228
228
My Function Output 4
1056
56
Cumulative Run-time Alarm
1230
230
My Function Output 5
1058
58
ProfiBus/DeviceNet/CC-Link Communication Error 1232
232
My Function Output 6
1060
60
Forward/Reverse Switching
1234
234
My Function Output 7
1062
62
Ready for Operation 1
1236
236
My Function Output 8
1064
64
Ready for Operation 2
1238
238
My Function Output 9
1068
68
Brake Release (BR)
1240
240
My Function Output 10
1070
70
Alarm Status Active
1242
242
My Function Output 11
1072
72
Forward Speed Limit (Torque Control)
1244
244
My Function Output 12
1074
74
Reverse Speed Limit (Torque Control)
1246
246
My Function Output 13
1076
76
ASD Healthy Output
1248
248
My Function Output 14
1078
78
RS485 Communication Error
1250
250
My Function Output 15
1080
80
Error Code Output 1
1252
252
My Function Output 16
1082
82
Error Code Output 2
1254
254
Always Off
1084
84
Error Code Output 3
Note:
Only positive logic is available for the listed parameters.