194
H9 ASD Installation and Operation Manual
Pulse Output Frequency
Program
Terminal
Analog Output Terminals
This parameter scales the
FP
output terminal by setting the pulses-per-second
output signal of the
FP
terminal.
See
F676
for more information on this parameter.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3.84
Changeable During Run —
Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FM Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to select the type of output signal provided at the
FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See
F005
for more information on this setting.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type —
Selection List
Factory Default —
0–10V
Changeable During Run —
No
FM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
FM
output terminal. The
FM
output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See
F005
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F682
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
FM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
FM
terminal.
Set the function of
F005
to zero and then set this parameter to zero for proper
operation.
See
F005
for more information on this setting.
Direct Access Number — F683
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
AM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
AM
output terminal.
The
AM
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F670
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F685
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
F677
F685