H9 ASD Installation and Operation Manual
Virtual Input Terminal 1 Selection
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
Virtual Input Terminal
1
.
As a virtual terminal, it exists only in memory and is considered to always be in
its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
Virtual Input Terminal
1
terminal to
one of the functions that are listed in
Table 5 on pg. 234
.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F973
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Virtual Input Terminal 2 Selection
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
Virtual Input Terminal
2
.
As a virtual terminal, it exists only in memory and is considered to always be in
its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
Virtual Input Terminal
2
terminal to
one of the functions that are listed in
Table 5 on pg. 234
.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F974
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Virtual Input Terminal 3 Selection
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
Virtual Input Terminal
3
.
As a virtual terminal, it exists only in memory and is considered to always be in
its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
Virtual Input Terminal
3
terminal to
one of the functions that are listed in
Table 5 on pg. 234
.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F975
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Virtual Input Terminal 4 Selection
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
Virtual Input Terminal
4
.
As a virtual terminal, it exists only in memory and is considered to always be in
its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
Virtual Input Terminal
4
terminal to
one of the functions that are listed in
Table 5 on pg. 234
.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F976
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
F973
F976