H9 ASD Installation and Operation Manual
19
Figure 4. The
Grounding Capacitor
Switch
is used on typeforms
230-
volt
0.75 HP to 10 HP and the 25
and 30 HP/
460-volt
1.0 HP to 25 HP.
The value may be set to
Maximum
(default setting) or to
Zero
by
pushing or pulling the switch
actuator, respectively.
Figure 5. The
Grounding Capacitor
Switch
is used on typeforms
230-
volt
15 HP to 20 HP and the 40 HP to
60 HP/
460-volt
30 HP to 100 HP.
The value may be set to
Large
(default setting) or
Small
by pushing
or pulling the switch actuator,
respectively.
Figure 6. The
Grounding Capacitor
Bar
is used on typeforms
230-volt
75 HP and the 100 HP/
460-volt
125
HP and the 150 HP.
The value may be set to
Large
or
Small
(default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. The
Grounding Capacitor
Screw
is used on typeforms
460-volt
200 HP and above.
The value may be set to
Large
or
Small
(default setting) by placing the
screw in the
A
position or by placing
the screw in the
B
position,
respectively.