H9 ASD Installation and Operation Manual
131
Jump Frequency 1 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 1
(see
F270
).
Direct Access Number — F271
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program
Special
Jump Frequencies
Same as
Jump Frequency 1
(
F270
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
F273
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F272
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Jump Frequency 2 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 2
(
F272
).
Direct Access Number — F273
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
Special
Jump Frequencies
Same as
Jump Frequency 1
(
F270
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
F275
).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
Jump Frequency 3 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 3
(
F274
).
Direct Access Number — F275
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Preset Speed 8
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as
Preset Speed 8
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F287
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
F271
F287