H9 ASD Installation and Operation Manual
139
Synchronized Acceleration Time
Program
Protection
Under-Voltage/Ridethrough
In the event that the
Ridethrough
function activates in a multiple-motor
application it will be necessary to manage the accelerating motors
synchronously as not to damage the product being processed (e.g., wire spools,
bobbin winder for textile machines, etc.).
This parameter is used to minimize the product breakage during a momentary
power outage. This function orchestrates the acceleration of multiple machines
simultaneously or makes them reach their respective command frequencies
simultaneously by regulating their acceleration times.
See parameter
F302
for more information on this setting.
Direct Access Number — F318
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 6000
Units — Seconds
Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the effective 100% output torque level while operating in
the
Drooping Control
mode. This value is the upper torque limit of the motor
being driven by a given ASD while operating in the
Drooping Control
mode.
Note:
The maximum frequency output is not limited by the setting of
F011
while operating in the
Drooping Control
mode.
Drooping
Drooping
Control
, also called
Load Share
, is used to share the load among
two or more mechanically coupled motors. Unlike
Stall
, which reduces the
output frequency in order to limit the load once the load reaches a preset level,
Drooping
can decrease or increase the V/f setting of a motor to maintain a
balance between the output torque levels of mechanically coupled motors.
Because of variances in gearboxes, sheaves, belts, motors, and since the speed
of the motor is constrained by the mechanical system, one motor may
experience more load than its counterpart and may become overloaded.
Drooping
Control
allows the overloaded motor to slow down, thus shedding
load and encouraging a lightly-loaded motor to pick up the slack. The goal of
Drooping
Control
is to have the same torque ratios for mechanically coupled
motors.
Direct Access Number — F320
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Speed at 0% Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 0% output torque gain while
operating in the
Drooping
Control
mode. This function determines the lowest
speed that
Drooping
will be in effect for motors that share the same load.
Direct Access Number — F321
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 320.0
Units — Hz
Speed at
F320
Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 100% output torque gain while
operating in the
Drooping
Control
mode. This function determines the speed
of the individual motors at the 100%
Drooping Gain
setting for motors that
share the same load.
Direct Access Number — F322
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 320.0
Units — Hz
F318
F322
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]