H9 ASD Installation and Operation Manual
233
Traverse Selection
Program
Special
Traverse
This parameter setting is used in the setup of the
Traverse
control mode of
operation and is used in conjunction with the discrete terminal activation of the
Traverse Permission Signal
.
This parameter is used to enable the
Traverse
function. The
Traverse
function
is activated via the discrete input terminal (see
Table 5 on pg. 234
).
See the
Traverse Control Instruction Manual
(P/N 58693) for more
information on this feature.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F980
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Traverse Acceleration Time
Program
Special
Traverse
This parameter setting is used in the setup of the
Traverse
control mode of
operation. This setting establishes the acceleration rate used during the
Traverse
function.
See the
Traverse Control Instruction Manual
(P/N 58693) for more
information on this feature.
Direct Access Number — F981
Parameter Type —
Numerical
Factory Default —
25.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 120.0
Units — Seconds
Traverse Deceleration Time
Program
Special
Traverse
This parameter setting is used in the setup of the
Traverse
control mode of
operation. This setting establishes the deceleration rate used during the
Traverse
function.
See the
Traverse Control Instruction Manual
(P/N 58693) for more
information on this feature.
Direct Access Number — F982
Parameter Type —
Numerical
Factory Default —
25.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 120.0
Units — Seconds
Traverse Step
Program
Special
Traverse
This parameter setting is used in the setup of the
Traverse
control mode of
operation. This setting is used as a multiplier to establish the amount that the
frequency is increased or decreased while using the
Traverse
function.
See the
Traverse Control Instruction Manual
(P/N 58693) for more
information on this feature.
Direct Access Number — F983
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 25.0
Units — %
Traverse Jump Step
Program
Special
Traverse
This parameter setting is used in the setup of the
Traverse
control mode of
operation. This setting is used as a multiplier to establish the amount that the
frequency is increased or decreased while using the
Traverse
function when a
short burst of rapid speed change is required.
See the
Traverse Control Instruction Manual
(P/N 58693) for more
information on this feature.
Direct Access Number — F984
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 50.0
Units — %