By pressing the [SERVICE] button of the water heater, the water heater can be started without a heating de-
mand. The water heater will start to fire and also the pump will start to run. Firing of the water heater without a
water flow (but filled with water!) will cause the so called “boiling noises”. Check during this “service function”
operation also the flow and return temperatures of the water heater
by pressing the [◄] button once. The tem-
perature difference of the flow and return must be at least 13ºC and maximum 25ºC. This temperature difference
indicates that there is a (enough) water flow over the water heater; this water flow prevents the heat exchanger
of possible damage caused by a thermal overload.
Flow monitoring
Another safety feature of the water heater, to make sure that there is enough water flow over the water heater, is
the monitoring of the flow and return temperatures (T1 and T2). When the temperature difference (delta T) be-
tween flow and return exceeds a certain (set) value (load dependent), the following warning messages will be
shown in the display.
Display message
T 1
- T 2
h i
g h
9 9 9
,
5
h r s
Reason
Temperature difference T1-T2 has exceeded the blocking value, as set in the pa-
rameters.
Display message
D e
l
t
a
D i
r e c
t
b
l
o c k
9 9 9
,
5
h r s
Reason
The temperature difference between flow and return has exceeded the blocking
value
When this temperature difference exceeds the lock-out setting, the water heater will switch off and the following
lock out code will be shown at the display.
Display message
F
l
o w R e
t u r n
d t
f
a u
l
t
F16
p u m p
o n
9 9 9
,
5
h r s
Reason
Temperature difference between flow and return has exceeded the blocking value.
Parameters P2CO, P2CR until P2CV.
When these messages appear and/or the water heater will lock out, it means that there is not enough flow over
the water heater. In this case check the functioning of the pump.
The water heater has a built in water pressure switch. If water pressure of the system drops under a certain limit,
the water heater will go in a lock-out.
During and after the commissioning of the water heater, the operation of the water heater pump must be
checked, before leaving the installation room.
NOTICE: Always check the running of the pump before firing the water heater.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......