E09.012.246 Manual S-WG
112
16.2
Blocking codes
The display is not blinking, but is lightened up during the blocking period.
The water heater is blocking an action, because of an extraordinary situation. This action will be con-
tinued after eliminating the extraordinary situation.
Display message
F l o w
t e m p
h i g h
9 9 9 , 5
h r s
Reason:
Flow temperature has exceeded the blocking temperature, but it
has not exceeded the lock-out value.
Cause:
The water flow is restricted.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences the flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Display message
R e t u r n
t e m p
h i g h
9 9 9 , 5
h r s
Reason
Return temperature has exceeded the blocking temperature, but it
has not exceeded the lock-out value.
Cause:
Systems that pre-heats the water heater return temperature too much/high.
Corrective action:
Reduce pre heat temperature of external heat source.
Cause:
The need for heat in the system suddenly drops causing hot return water to the water
heater.
Corrective action:
Dampen external heating system control to prevent sudden water heater temperature
rise.
Display message
F l u e
t e m p
h i g h
9 9 9 , 5
h r s
Reason
Flue gas temperature has exceeded the limit.
Cause:
Heat exchanger polluted and not able to transfer enough heat to the system water.
Corrective action:
Check and clean heat exchanger.
Cause:
Bad flue gas sensor or sensor connection (partly shorted.)
Corrective action:
The sensor is of the type NTC. This means that its resistance gets lower when the tem-
perature rises. A partly shorted sensor will drop resistance and therefore
‘measure’ a
higher temperature.
Check for moist in the sensor connections or replace the sensor.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......