E09.012.246 Manual S-WG
85
Display message
F9
F l a m e
l o s t
p u m p
o n
9 9 9 , 5
h r s
Reason
Flame detected during normal operation, but was lost while running.
Display message
F10
F a l s e
f
l a m e
s i g n a l
p u m p
o n
9 9 9 , 5
h r s
Reason
Flame signal is detected while it cannot be expected.
Display message
F11
F a n
s p e e d
i n c o r r e c t
p u m p
o n
9 9 9 , 5
h r s
Reason
The controller does not detect a correct fan speed.
Display message
F12
p r o g r a m m i n g
e n d
p u m p
o n
9 9 9 , 5
h r s
Reason
Software parameters have been programmed.
Display message
F13
P a r a m / H a r d w
f a u l
t
p u m p
o n
9 9 9 , 5
h r s
Reason
Fault during programming of the water heater software parameters.
Display message
F14
H i g h
G a s
F a i
l
p u m p
o n
9 9 9 , 5
h r s
Reason
Gas supply pressure is too high.
Display message
F15
C l
i x o n
F a u l t
p u m p
o n
9 9 9 , 5
h r s
Reason
Rear wall thermostat (clixon) detects a too high temperature.
Display message
F16
F l o w R e t u r n
d t
f a u l
t
p u m p
o n
9 9 9 , 5
h r s
Reason
Temperature difference T1-T2 has exceeded the blocking value.
Programmed at the parameters P2 CO, P2 CR until P2 CV.
Display message
F17
W a t e r
h i g h
l
i m i
t
p u m p
o n
9 9 9 , 5
h r s
Reason
Maximum thermostat (clixon) measured a too high flow temperature.
Display message
F19
S i p h o n
s w i
t c h
p u m p
o n
9 9 9 , 5
h r s
Reason
The pressure switch detects a high pressure in the flue/siphon system.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......