
E09.012.246 Manual S-WG
81
Menu C: Cascade
C 2
B u s
a d r e s s
0
Function for the cascading of the boiler(s).
This parameter determines the address of the boiler
for the total cascading control.
Master = 0, Slave 1 = 1 etc.
Menu C: Cascade
C 3
D H i c a s / m a s
0
Function for the cascading of the boiler(s).
This parameter determines if only the Master boiler or all
boilers of the cascade are used for indirect hot water.
0 = All
1 = Master
Menu C: Cascade
C 4
E x t r a u n i t
0
Function for the cascading of the boiler(s).
This parameter is activated when an external (extra) boiler
is connected to the Master boiler. Connect to the Master
connections 21-22.
Menu C: Cascade
C 5
C a s
S i / M a
0
Function for the cascading of the boiler(s).
This parameter sets the function of the boiler at a cascade
alignment
0 = Single / Slave unit
1 = Master unit
Menu C: Cascade
C 6
P w r O f f T o C a
0
Function for the cascading of the boiler(s).
This parameter determines the function of the Slave boilers
when the Master boiler is switched off.
0 = Slave boiler(s) continue operation
1 = Slave boiler(s) switch off
Menu C: Cascade
C 7
C o m F l u N u m
0
Function for the cascading of the boiler(s).
This parameter determines the number of cascaded boilers,
that are implemented with a common flue system.
The screen texts on these pages are
standard part of the software and
apply to CH systems (boilers) and/or
DHW devices (water heaters).
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......