E09.012.246 Manual S-WG
82
Menu D: General
D 1
0 - 1 0 V c o n t
r
0
Function for the external control of the boiler by using
a 0-10 Volt signal (Connections 15-16).
0 = No external control
1 = Control based on temperature setting
2 = Control based on power setting
Menu D: General
D 2
0 - 1 0 M i n T m p
2 0
° C
Function for the external control of the boiler by using
a 0-10 Volt signal (Connections 15-16).
Control based on temperature (setting 1).
The minimum (desired) CH water temperature when
supplying a 1 Volt signal.
Menu D: General
D 3
A l
t
*
1 0 0 f
0
Function for setting the location height (above sea level)
of the boiler.
NOTICE: dimensions in English feet. One unit = 100 ft.
Use this function only in consultation with the supplier/manu-
facturer.
Menu D: General
D 4
M a x C o o l T i m
2 M i n
Function for setting the maximum overrun time of the fan
(Maximum 10 minutes).
0 = Switch off
Menu D: General
D 5
T e m p O n D i s p
1
Function to show the (measured) temperature of the boiler at
the display.
Menu D: General
D 6
D H
W
1 = i 2 = d
1
Function to set up the CH and HW boiler options.
0 = CH only (direct)
1 = CH/HW function (indirect)
2 = HW only (direct)
The screen texts on these
pages are standard part of the
software and apply to CH sys-
tems (boilers) and/or DHW
devices (water heaters).
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......