80
Menu B: Hot water
B B
D H d s c D i f 2
1 0
° C
Function for the direct hot water boiler.
This parameter is the hysteresis of the selected
HW temperature of the boiler.
Menu B: Hot water
B C
D H d s c l n t 2 3
2 0 0 S e c
Function for the direct hot water boiler.
This parameter is the integration time of the selected
HW temperature of the boiler.
Menu B: Hot water
B D
D H d s c O f f 3
4
° C
Function for the cascaded direct hot water boilers.
This parameter is the offset of the selected
HW temperature of the cascaded boilers.
Menu B: Hot water
B E
D H d s c D i f 3
8
° C
Function for the cascaded direct hot water boilers.
This parameter is the hysteresis of the selected
HW temperature of the cascaded boilers.
Menu B: Hot water
B F
D H i s c D i f 4
5
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter is the hysteresis of the selected
HW temperature of the calorifier/tank.
Menu B: Hot water
B G
D H i d e t g r a d
3
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter detects an (an accelerated) hot water
demand, when a larger (water) amount is being used.
Menu C: Cascade
C 1
M a x C a s c U n t
1 1
Function for the cascading of the boiler(s).
This parameter sets the total amount of cascaded boilers.
(Max. 12 boilers).
The screen texts on these pages are
standard part of the software and
apply to CH systems (boilers) and/or
DHW devices (water heaters).
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......