E09.012.246 Manual S-WG
114
Display message
L i n e
f a u l t
p u m p
o n
9 9 9 , 5
h r s
Reason
Bad power supply
Cause:
The supplied power does not comply with the specifications.
Corrective action:
Check if the power supply is connected correctly to the unit.
Check the voltage and frequency (should be Life Neutral, Gnd > 230Vac/50Hz).
Make sure there is no signal failing or voltage peaks in the power supply.
Display message
T 1 - T 2
h i g h
9 9 9 , 5
h r s
Reason
Difference between T1 and T2 has exceeded the blocking value
which has been set in the parameters.
Cause:
The water flow through the unit is too low.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Make sure the heat exchanger is clean. Heat exchanger fouling (partly blockage) will
increase the resistance causing the water flow to drop.
Display message
D e l
t a
D i r e c t
b l o c k
9 9 9 , 5
h r s
Reason
Temperature difference between flow and return has exceeded
the blocking value
Cause:
The water flow through the unit is too low.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences the flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Make sure the heat exchanger is clean. Heat exchanger fouling (partly blockage) will
increase the resistance causing the water flow to drop.
Display message
H e a t e x c h a n g
a t
r i s k
9 9 9 , 5
h r s
Reason
Temperature difference between flow and return has exceeded
the blocking value 3 times (P2LL = 2)
Cause:
Low water flow.
Corrective action:
Clean the heat exchanger on the water side. Heat exchanger fouling (partly blockage) will
increase the resistance causing the water flow to drop.
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences the flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......